The preparing capacity for this models just depends the dosing flow rate and for that is recommendable to understand the indicated volume as a hourly capacity, assuming 60 minutes maturation time, which is the standard for most polyelectrolyte manufacturers.
Main structure built in HDPE, with two chambers parallelepiped geometry connected by overflowย channels permitting distinct solution volumes for, maturation and dosing. Pre-dilution system byย static mixer in feed water line.
The duty cycle is controlled by ultrasonic continues level measuring sensor, installed in the dosingย chamber, that start the refilling process automatically, opening the solenoid valve and adjustingย the dosing pump speed to get always the selected concentration even with water flow variations.
Configurable process alarms with informative or impeditive action. Mechanical and process fault alarms with independent contact free current signals.
Standard models cover most part of process needs but our engineering department can study with costumers different options to improve present configurations to any situation.
Reviews